How To Exam?

a knowledge trading engine...


Visvesvaraya Technological University (VTU) 2007 B.E Electrical and Electronics Engineering 6TH SEM POWER SYSTEM ANALYSIS AND STABILITY - Question Paper

Wednesday, 12 June 2013 01:50Web



Sixth Semester B.E. Degree Examination, Dec. 07 / Jan. 08 Power System Analysis and Stability Time: 3 hrs.    Max. Marks: 100

Note : I. Answer any FIVE full questions.

2. Assume missing data suitably.

1 a. Prove that p.u. value of reactance of a transformer is same whether reffered to H.T or L.T.

(05 Marks)

b. Three pans of a single-phase electric system are designated A, B and C and are connected to each other through transformers as shown in Figl(b) below . The transformers are rated as follows :

A-B : 10 MVA, 13.8 - 138 KV, X = 10%

B - C : 10 MVA, 69- 138 KV, X - 8%

t-f;J-1

t\- &


&    fjii t is***-

Fig. 1(b)

If the base in the circuit B* is chosen as 10 MVA, 138KV find the p.u. impedance of the 300Q resistive load in circuit C* reffered to circuit C,B and A. Draw the impedance diagram neglecting magnetizing current, transformer resistance, lire impedance. Determine the voltage regulation if the voltage at the load is 66KV, with the assumption that voltage input to circuit remains constant.    r 15 Marks)

A sudden 3-phase short circuit takes place at the terminals of an unloaded three-phase alternator. Discuss briefly on the different reactances that are met with, assuming that the damper windings are provided at the pole-faces of salient pole synchronous machine.

(07 Marks)

From Bus admittance matrix for the svstem given below.

Bus-code

Zpq

p-q

1-2

j0.24

2-3

j0.18

3-1

JO.06

(07 Marks)

c. Write briefly on Selection of C.B*    " (06 Marks)

a.    Derive an expression for the three-phase complex power in terms of the sequence components and hence show that the symmetrical component transformation is power invariant.    (06 Marks)

b.    One conductor of a three-phase line is open. The current flowing to the A -connected load through line 'a' is 10 A. With the current in line a as reference and assuming thai line c is open, find symmetrical components of the line currents.

&



/* R.


tL6J

*

a.    Wuh the help of relevant phasor-diagrams of voltages, show that there exists a phase shift of positive and negative sequence components in a three-phase Y-A transformer bank. Assume H T. side to be Y-connected and L.T. side A connccted.    (06 Marks)

b.    A 25 MY A, 13.2 KV alternator with solidly grounded neutral has a sub-transient reactance of 0.25 p.u. The negative and Zero sequence reactances are 0.35 andO.l p.u respectively. A single line to ground fault occurs at the terminals of an unloaded'alternator, determine the fault current.    ;    (06 Marks)

c.    A 3-phase generator rated 15 MVA, 13.2 KV has a solidly grounded neutral. Its +ve, -ve, and o sequence reactance are 40%, 30%, 5%respectively.

i)    Find the value of reactance to be connected in the neutral circuit so that fault current for a single line to ground fault, does not exceed the rated line current (Zf= o).

ii)    Find the value of resistance to be connected in the neutral circuit to serve the same purpose.    (08 Marks)

a.    A generator with grounded neutral has sequence impedance of Z|, Z2 and Zo and generated emf(E), If a single-line to ground fault occurs on terminals of phase a, find Vb and Vc (Zf= 0).    (06 Marks)

b.    Show that the Impedance Zn between the Y-neutral and ground of a 3<f> machine is represented equivalently as 3Zn in its zero sequence diagram.    (8 Marks)

c.    Draw the interconnection of sequence network for a double-line to ground fault. (06 Marks)

a. A 5 MVA, 6.6KV alternator with a reactance of 8% is connected to a feeder of series

impedance of 0.12 + j0.48Qs/phase/km. The transformer is rated at 3 MVA, 6.6KV/33KV and has a reactance of 5%. Determine the fault current supplied by the generator operating under no-load, with a voltage of 6.9 KV, when a 3-<|> symmetrical fault occurs at a point 15 km along the feeder.

3aWfr Fig.6(a)

Choose generator ratings as base values.    (10 Marks)

b.    A synchronous generator and motor are rated for 30 MVA, 13.2KV and both have subtransient reactance of 20%. The line connecting them has a reactance of 10% on the base of machine, ratings. The motor is arawing 20 MW at 0.8 p.f (jead). The. terminal voltage of the motor is 12.8KV. When a symmetrical 3cJ> fault occurs at motor terminals, find the subtransient current in - i) Generator    ii) Motor.    (10 Maries)

a. Explain the concept of: i) Steady state stability ii) Transient stability.    (06 Marks)

h Define M and H constants of a synchronous machine. Hence develop the relation between them.    (06 Marks)

c.    A 2- pole, 50HZ, 11KV, turbogenerator has a rating of 60 MW and p.f of 0.85(log). Its rotor has a moment of inertia 8800 kg-m2. Find:

i) Its interia constant in MJ/MVA ii) Momentum in MJ-S/elect. degree. (08 Marks)

a.    With a neat sketch, explain equal area criteria for finding stability limit.    (05Marks)

b.    Develop the expression for critical clearing angle for a fault on a double feed or power system.

c.    A 50Hz, generator is supplying 50% of the power that it is capable of delivering through a transmission line to an infinite bus. A fault occurs that increases the reactance between the generator and the in-finite bus to 500% of the value before fault. When the fault is isolated, the maximum power that can be delivered is 75% of the original maximum value. Determine critical clearing angle (5 l)-    (10 Marks)








Attachment:

( 0 Votes )

Add comment


Security code
Refresh

Earning:   Approval pending.
You are here: PAPER Visvesvaraya Technological University (VTU) 2007 B.E Electrical and Electronics Engineering 6TH SEM POWER SYSTEM ANALYSIS AND STABILITY - Question Paper